Energy Automation

Every factory runs two production lines. The first one makes your product. The second one is invisible: it makes heat nobody uses, compressed air that hisses out of tired fittings, motors that spin at full speed when half would do, and demand spikes that set your electricity bill for the whole month. You pay for both lines, but only one of them earns you money.

This guide is about shutting down that second line. If you want to reduce energy costs in manufacturing, the biggest levers are usually the same: understand how you are billed, measure before you spend, fix compressed air, put motors on a diet, move flexible loads out of peak periods, and keep the savings with monitoring and automation. None of it needs a new factory. Most of it starts with data and a fresh look at things you walk past every day.

Key takeaways

  • In industry, electric motor systems use about 72% of electricity, so motors, pumps, fans and compressors are where the money is.
  • Compressed air leaks can waste 20 to 30% of a compressor’s output in a poorly maintained plant. A well-run system keeps leakage below 10%.
  • Slowing a fan or pump by 20% with a variable speed drive can cut its power draw by about half.
  • On industrial tariffs, when you use power matters as much as how much: peak periods, the June to August high-demand season and maximum demand charges all shape your bill.
  • Measured savings can still qualify for the Section 12L tax incentive, which now runs until 31 December 2030.

Why manufacturing energy costs bite harder in South Africa

Three things make energy a bigger line item for South African manufacturers than it used to be.

Prices keep climbing. Eskom’s tariffs for direct customers rose by an average of 8.76% on 1 April 2026, and municipal customers saw an average increase of 9.01% from 1 July 2026, according to Eskom’s announcement of the NERSA decision. A factory that does nothing pays more every year for exactly the same output.

Timing costs money. Large-power tariffs charge different rates for peak, standard and off-peak periods, and winter costs more. On Eskom’s Megaflex tariff, the high-demand season runs from 1 June to 31 August. In 2025 Eskom also reshaped its time-of-use periods: evening peaks grew from two hours to three, and morning peaks shrank from three hours to two, as set out in its 2025/26 tariff booklet. If your shift pattern has not changed since then, you may be running heavy loads in the most expensive hours of the day.

Demand charges punish spikes. Many industrial bills include a charge based on your highest demand in the month. One careless start-up, when every motor kicks in at once, can set that charge for the next 30 days.

72%

of industrial electricity is used by electric motor systems, according to the IEA 4E Electric Motor Systems Platform. If you want to cut factory energy costs, start with the things that spin.

Step 1: Read your bill like an engineer

Before you buy anything, understand what you are paying for. An industrial electricity bill is not one number. It is several charges, and each one responds to a different action.

Bill componentWhat drives itYour lever
Energy charge (kWh)How much you use, and in which time-of-use periodEfficiency upgrades and shifting flexible loads to off-peak
Demand charge (kVA)Your highest average demand in the chargeable periodsStaggered start-ups and load control during peaks
Reactive energy chargePoor power factor, usually from motors and inductive loadsPower factor correction
Capacity and network chargesThe capacity you have reserved with the utilityReview notified demand against actual use
Seasonal pricingHigher rates in the June to August high-demand seasonPlan maintenance shutdowns and heavy batches around winter peaks

Each charge needs a different fix. Treating the bill as one number hides the cheapest savings.

A tariff review is often the fastest win of all, because it costs nothing to implement. Energyrite’s tariff analysis and bill audits check whether you are on the right tariff and whether you are paying for errors. Our guide to peak-hour charges explains why the same kilowatt-hour can cost several times more depending on when you use it.

Step 2: Measure before you move

You cannot manage what you cannot see, and a monthly bill is a very blurry picture. A factory needs interval data, ideally every 5 to 15 minutes, and sub-metering on the biggest loads: compressors, chillers, furnaces, extruders, pumps and dust extraction.

Once the data starts flowing, three things usually jump out:

  • The weekend mystery. The plant is closed, yet usage on a Sunday can still be 30 or 40% of a weekday. Something is running that should not be.
  • The Monday spike. Every machine starts at 07:00 and the demand meter records the highest peak of the month.
  • The silent drift. One line slowly uses more energy per unit produced, a sign of wear, blockages or poor settings.

Smart meters and sub-meters are the foundation of everything that follows. Our article on smart meters and sub-metering explains how they work, and Energyrite’s real-time monitoring records your usage at 5-minute intervals. If you want a structured starting point, our guide to energy audit software versus a professional energy audit explains how to combine both.

Try this today

Walk the plant 30 minutes after the last shift ends. Listen and look. Anything humming, hissing, glowing or blowing air is costing you money while producing nothing. Write it down, then check it against your data next week.

Step 3: Put your motors on a diet

Motors drive pumps, fans, conveyors, mixers and compressors, and in most plants they are the single biggest energy user. The good news is that small changes to motor systems produce big savings.

Use variable speed drives where the load varies

Many fans and pumps run at full speed, with a damper or valve throttling the flow. That is like driving with one foot on the accelerator and the other on the brake. A variable speed drive (VSD) slows the motor down instead. Because of the affinity laws, the savings are dramatic: the US Department of Energy notes that reducing a fan or pump’s speed by 20% can cut its input power by about 50%.

Right-size, maintain and upgrade

  • Right-size: an oversized motor running at light load wastes energy all day.
  • Maintain: worn belts, poor alignment and failing bearings all add friction you pay for.
  • Upgrade at failure: when a motor fails, compare the life-cycle cost of a premium-efficiency replacement with a rewind. The energy bill over the motor’s life usually dwarfs the purchase price.
  • Switch off: conveyors, extraction fans and pumps that run between batches can often be interlocked or automated to stop when not needed.

The cheapest kilowatt-hour is the one your motor never uses because it was switched off or slowed down.

Step 4: Stop paying for compressed air leaks

Compressed air is often called the most expensive utility in a factory, because most of the electricity a compressor uses turns into heat rather than useful air. Then much of the air that is produced leaks away.

According to the Compressed Air Challenge leak fact sheet, leaks can waste 20 to 30% of a compressor’s output, and a well-maintained system should lose less than 10%. That means in many plants, one compressor out of every four or five is running only to feed leaks.

How to run a leak hunt

  1. Pick a quiet time. On a Sunday or after the last shift, with production stopped, leaks are easy to hear.
  2. Measure the leak load. With no production running, any air the compressor still supplies is going into leaks.
  3. Tag every leak. Use bright tags, and use an ultrasonic leak detector for the ones you cannot hear.
  4. Fix them fast. Most leaks are fittings, hoses, couplings and drains, and many are cheap to repair.
  5. Lower the pressure. Many systems run higher than they need to. Natural Resources Canada’s rule of thumb is that every 2 psi of extra discharge pressure adds about 1% to energy use.
  6. Repeat every quarter. Leaks come back, so make the hunt a routine.

Also look for inappropriate uses of compressed air, such as blowing down workbenches or cooling people. A brush, a fan or a low-pressure blower does the same job for a fraction of the energy.

Step 5: Shift and shave your peaks

Once you know your loads, look at when they run. Two simple ideas can make a big difference to an industrial bill.

  • Shift: move flexible loads such as batch processes, pumping to storage tanks, charging forklifts and pre-heating into off-peak or standard periods. Our guide to tariff-based automation shows how to do this automatically rather than relying on someone to remember.
  • Shave: avoid the monthly demand spike by staggering start-ups after breaks and shift changes, and by briefly holding back non-critical loads when demand gets close to a set limit.

Not every load is worth automating. Our list of loads worth automating first helps you choose, and our article on which energy automation projects pay back fastest helps you rank them. Energyrite’s automation solutions combine schedules and rules so the plant runs to the tariff without extra work for your team.

Plan for outages, too

When the grid goes down, a badly planned restart can create the biggest spike of the month and damage equipment. Restart loads in stages, keep critical systems on backup power and track your diesel. Our guide to automation for load shedding and outages covers safe restart sequences, and Energyrite’s loadside solutions include diesel, water and temperature monitoring.

Step 6: Heat, cooling and lighting

Process heat and hot water

Uninsulated pipes, valves and tanks lose heat all day. Insulating them is one of the simplest projects with a fast payback. Also look for heat you can recover: compressors, refrigeration plant and ovens all reject heat that can pre-heat water or space.

Cooling and ventilation

Chillers, cold rooms and air conditioning work harder when filters and coils are dirty or when set points drift. Schedules, set point limits and good maintenance pay off quickly. Our guide to HVAC automation to cut air-conditioning costs covers the controls side.

Lighting

High-bay LED fittings with occupancy and daylight sensors are now standard for warehouses and production halls. They cut energy use and last longer, which matters when replacing a lamp means hiring a scissor lift. See our article on lighting automation savings.

Power factor

Motors and other inductive loads lower your power factor, which can show up as a reactive energy charge and a higher demand charge. Power factor correction equipment, properly sized and maintained, can reduce both. Check your bill for a reactive energy line before you decide.

Step 7: Get your people on board

Technology delivers the big savings, but people decide whether they last. Machines left idling between batches, doors propped open on cold rooms and lights left on in empty stores add up across hundreds of shifts.

  • Appoint energy champions on each shift and give them real data to work with.
  • Show the numbers: a screen with live consumption, or a weekly kWh-per-unit figure per line, changes behaviour fast.
  • Build energy into checklists: start-up, shutdown and changeover routines should include what to switch off.
  • Celebrate wins: share the savings and recognise the teams that delivered them.

Energyrite’s staff behavioural change programme helps teams turn energy awareness into daily habits.

A 90-day savings roadmap for your factory

Here is a practical way to sequence the work so that early wins pay for later projects.

WhenFocusActionsTypical cost
Days 1 to 30See and stopBill and tariff review, interval monitoring on the main incomer, after-hours walk-through, first leak huntLow
Days 31 to 60Fix the basicsRepair leaks, lower compressor pressure, fix schedules and set points, stagger start-ups, sub-meter big loadsLow to medium
Days 61 to 90Plan the big winsBusiness cases for VSDs, motor upgrades, power factor correction, heat recovery and LED lighting, using your own dataMedium to high
OngoingKeep the savingsAlerts, monthly reports, quarterly leak hunts and measurement and verification for Section 12LLow

Start with what costs nothing, prove the savings, then invest where the data says the payback is best.

Help with funding

Find out where your factory’s energy really goes

Energyrite combines 5-minute monitoring, alerts, automation and tariff analysis, so you can see the waste, stop it and prove the savings.

Book a free site walk-through

Myth: “Our machines need full power all the time.”

Very few processes need full flow or full speed all day. Fans, pumps and compressors often run far above what the process needs, which is why VSDs and better controls pay off so well.

Myth: “A few small leaks do not matter.”

Small leaks add up. In poorly maintained systems, leaks can account for 20 to 30% of compressor output, which in larger plants can mean a whole compressor running for nothing.

Myth: “Energy saving slows production down.”

Most savings come from removing waste: idling, leaks, poor settings and peak-time clashes. Done well, energy projects often improve reliability and product quality too.

The bottom line

Reducing energy costs in manufacturing is not about one big gadget. It is about switching off that invisible second production line, piece by piece. Read the bill, measure the plant, fix the air, slow the motors, dodge the peaks and bring your people along. Then keep watch, because savings that nobody monitors tend to disappear.

Want help getting started? Contact Energyrite or call 061 549 8534.

Frequently asked questions

What is the fastest way to reduce energy costs in manufacturing?

Start with a tariff and bill review, then add interval monitoring to find after-hours loads and demand spikes. Fixing compressed air leaks, correcting schedules and staggering start-ups usually deliver savings quickly and at low cost.

Which equipment uses the most energy in a factory?

Electric motor systems, which drive pumps, fans, compressors and conveyors, use about 72% of industrial electricity. Compressed air, process heating and cooling are also major users in many plants.

How much energy do compressed air leaks waste?

In a poorly maintained system, leaks can waste 20 to 30% of a compressor’s output. A well-maintained system should keep leakage below 10% through regular leak hunts and repairs.

Do variable speed drives really save energy?

Yes, on variable loads such as fans and pumps. Because of the affinity laws, reducing a fan or pump’s speed by 20% can cut its input power by about half. They save little on constant loads that must run at full speed.

How can a factory reduce maximum demand charges?

Stagger the start-up of large motors after breaks and shift changes, move flexible loads out of peak periods, and use automation to hold back non-critical loads briefly when demand approaches a set limit.

Are there incentives for industrial energy efficiency in South Africa?

Yes. The Section 12L tax incentive for verified energy efficiency savings has been extended to 31 December 2030, and the National Cleaner Production Centre of South Africa offers energy assessments, training and technical support.

How do I know if my energy savings are real?

Measure a baseline before you change anything, then compare it with the results, adjusting for production volumes and weather. Continuous monitoring with interval data makes this simple and supports Section 12L claims.